The U.S. Chemical Safety and Hazard Investigation Board released a new safety video, “RIPE for Change,” urging broader adoption of remote isolation equipment at chemical facilities to more quickly and safely stop hazardous-material releases. The video draws on findings from the CSB’s 2024 safety study, “Remote Isolation of Process Equipment (R.I.P.E.),” and highlights lessons and recommendations to reduce risks to workers and the public.
Today, the U.S. Chemical Safety and Hazard Investigation Board (CSB; Washington, D.C.; www.csb.gov) released a new safety video emphasizing the need for greater use of remote isolation equipment at chemical facilities. The safety video, titled “RIPE for Change,” is based on the CSB’s 2024 safety study titled “Remote Isolation of Process Equipment,” (R.I.P.E.) and includes […]
The post CSB releases video on isolating releases of hazardous materials appeared first on Chemical Engineering.
Login to comment
Login1 comment
0 Replies
1 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
0 Replies
1. Fail-safe action. Spring-return, fail-closed actuators so loss of air or power drives the valve shut. A double-acting actuator that needs air to close can lose that air in the same fire.
2. Fire survivability. The valve should be fire-tested (API 607 for quarter-turn soft-seated valves), and the actuator, solenoid, and cabling inside the credible fire zone need fireproofing (API 2218 covers fireproofing practice) or fire-resistant cable rated for the closing time required.
3. Activation point. Put the close pushbutton where an operator can reach it without entering the release or fire area, typically the control room plus a field station at a safe distance. A valve only operable at the valve is not remote isolation.
4. Shutoff and testing. Specify seat leakage class for the duty (ANSI/FCI 70-2) and proof-test it. If the valve is credited as a safeguard in the HAZOP or LOPA, it needs a defined proof-test interval and, if it is part of a SIF, IEC 61511 lifecycle requirements. Partial-stroke testing helps with stuck valves but does not prove tight shutoff.
5. Placement. Locate the valve on the vessel nozzle side of the likely leak points (pump seals, flanges, instrument connections), so it isolates the inventory, not just the downstream piping.