A drum or bottle filler in a Class I area gets reviewed for the Division or Zone and the gas group. The temperature class gets less attention, and it's the one that bites when the line changes solvents.
The rule is simple: the marked T-code (maximum surface temperature) can't exceed the autoignition temperature of the gas or vapor that can be present (NEC 500.8). The lower steps of the table are close together:
T3 = 200 C T3A = 180 C T3B = 165 C T3C = 160 C T4 = 135 C T6 = 85 C
Diethyl ether has an AIT of about 160 C in NFPA 497, so T3 equipment that is fine for hexane is out once ether is in the product mix, and T4 is the usual pick. Carbon disulfide is around 90 C and needs T6.
Two places to check on a packaging line: 1. Motors on VFDs. The nameplate T-code may only cover sine-wave supply or a set speed range. Look for the inverter-duty marking and the speed range it covers; IEEE 1349 has guidance for motors in Class I Div 2. 2. Heat-seal jaws, shrink tunnels and anti-condensation heaters. They are often the hottest surface on the machine, and a retrofit heater can end up outside the original certification.
Poll: When a line changes product, who checks the T-code against the new material's AIT?