API Standard 521 sizes the external pool-fire case from the wetted surface area. Only the surface within 25 ft (7.6 m) of the fire source counts, which is usually grade or any level where a pool could form. Wetted area above that height isn't included. For liquid-full or partly full vessels, the heat input is Q = 21,000 F A^0.82 (Btu/h, with A in ft²) when there's adequate drainage and prompt firefighting, and Q = 34,500 F A^0.82 when there isn't. F is the environment factor, which can take credit for qualifying insulation or water spray.

The calculation itself is rarely the problem. The inputs are. Common mistakes are the wrong elevation reference for the 25 ft limit on elevated or skirted vessels, the wrong liquid level (normal level and high-high level can give very different areas), and insulation credit for jacketing that wouldn't survive a fire. It's also worth checking how "adequate drainage" is defined before you use the lower coefficient, because that choice changes the heat input by about 64%.