When a filler or palletizer HMI, drive, or PLC panel has to sit inside a classified area, NFPA 496 pressurization is often cheaper and easier to maintain than an explosionproof enclosure. The type is set by the area classification and by what's inside the box.
Type X takes the enclosure interior from Division 1 to unclassified, and it must de-energize the equipment automatically when purge pressure is lost. Type Y takes it from Division 1 to Division 2, so everything inside the enclosure still has to be suitable for Division 2. Type Z takes it from Division 2 to unclassified and only needs an alarm on loss of pressure.
Before power-up, the enclosure must be purged with at least four enclosure volumes of clean air or inert gas, then held at positive pressure (25 Pa, or 0.1 in. w.c., minimum).
Two failure modes come up often in washdown and corrosive service: purge air drawn from a contaminated header, and door gaskets that degrade under caustic or sanitizer and push purge consumption past the controller's flow limit. Also check whether moving the HMI outside the boundary and keeping only remote I/O in the classified area would remove the purge altogether.
Poll: For HMIs and drives on packaging lines in Division 1 areas, what's your default?